VFD energy savings calculator
Estimate how much energy, money and CO₂ a variable frequency drive saves on a pump or fan compared with valve or damper control — and see exactly how the figures are worked out.
What could a VFD save you?
For centrifugal pumps and fans the affinity laws apply: flow ∝ speed, pressure ∝ speed², power ∝ speed³. Throttling a valve or damper wastes that difference as heat and noise; a drive simply slows the motor down.
| Speed | Flow | Power |
|---|---|---|
| 100% | 100% | 100% |
| 90% | 90% | 73% |
| 80% | 80% | 51% |
| 70% | 70% | 34% |
| 60% | 60% | 22% |
Indicative estimate for centrifugal loads, 300 days/year, compared with valve/damper control at ~85% of rated power. Actual savings depend on your duty profile — we'll measure it for you.
The formulas
For centrifugal pumps, fans and blowers the affinity laws relate speed (N) to flow (Q), head or pressure (H) and shaft power (P):
H₂ / H₁ = (N₂ / N₁)²
P₂ / P₁ = (N₂ / N₁)³
The calculator compares two ways of getting the reduced flow:
Ethr = Prated × h × D × 0.85
With VFD (motor slowed to the needed speed)
Evfd = Prated × (N%/100)³ × h × D ÷ ηvfd
Savings
ΔE (kWh/yr) = Ethr − Evfd
Cost (₹/yr) = ΔE × tariff
CO₂ (t/yr) = ΔE × 0.71 ÷ 1000
What the numbers mean
| Symbol | Meaning | Value used |
|---|---|---|
| Prated | Motor rating | Slider (kW) |
| h | Running hours per day | Slider |
| N% | Average speed needed | Slider (50–100%) |
| D | Operating days per year | 300 |
| 0.85 | Power drawn when throttled, as a fraction of rated | Typical for valve/damper control |
| ηvfd | Drive efficiency | 0.97 |
| 0.71 | Grid emission factor (kg CO₂/kWh) | India grid average (CEA) |
Worked example
A 22 kW pump running 16 h/day at 80% speed, ₹9/kWh:
Evfd = 22 × 0.8³ × 16 × 300 ÷ 0.97 = 55,739 kWh
ΔE = 34,021 kWh/yr → ₹306,186/yr, 24.2 t CO₂
Constant-torque loads (conveyors, compressors, extruders) don't follow the cube law; savings there come mainly from soft starting and matching speed to demand. For an accurate figure we log your actual load profile.
Want a measured savings report?
We log your motor's real load for a week and give you a payback calculation for a VFD retrofit.